Harmonic Distortion Calculator supports engineering calculations with transparent assumptions, practical result interpretation, and links to next-step technical resources.
THD = sqrt(sum(Ih^2)) / I1 x 100%
TDD = sqrt(sum(Ih^2)) / IL x 100% (current only)
K-factor = sum(h^2 x (Ih / I1)^2) + 1
Enter RMS magnitudes for each harmonic order. The spectrum and summary metrics update in real time.
THD Result
—
Dominant Harmonic
—
Compliance Check
—
Total Harmonic RMS
—
Total RMS
—
Distortion Factor
—
Harmonic Energy Share
—
TDD
—
K-factor
—
| Order | RMS V | % of Fundamental | Contribution |
|---|---|---|---|
| H2 | — | — | |
| H3 | — | — | |
| H4 | — | — | |
| H5 | — | — | |
| H6 | — | — | |
| H7 | — | — | |
| H8 | — | — | |
| H9 | — | — | |
| H10 | — | — | |
| H11 | — | — | |
| H12 | — | — | |
| H13 | — | — | |
| H14 | — | — | |
| H15 | — | — |
THD vs TDD
THD is normalized to fundamental amplitude. TDD is normalized to maximum demand current and is often preferred for current-distortion compliance discussions.
Dominant Order Identification
Pinpointing the strongest harmonic order helps you decide between source reactors, passive filters, active filtering, or distribution-level mitigation.
| Topic | Equation | Meaning |
|---|---|---|
| Total harmonic distortion (THD) | THD (%) = sqrt(sum(Ih^2)) / I1 x 100 | Compares total RMS harmonic content to the fundamental component. |
| Total demand distortion (TDD) | TDD (%) = sqrt(sum(Ih^2)) / IL x 100 | Current-only metric referenced to maximum demand current instead of fundamental current. |
| Distortion factor | DF = I1 / Irms = 1 / sqrt(1 + THD^2) | Indicates how much of total RMS remains in the fundamental component. |
| Transformer K-factor (screening) | K = 1 + sum(h^2 x (Ih / I1)^2) | Weights higher-order harmonic currents more heavily for thermal stress indication. |
| Scenario | Objective | Recommendation | Critical Checks |
|---|---|---|---|
| Drive-heavy panel commissioning | Identify dominant harmonic orders from multiple VFD-fed motor branches | Enter measured harmonic RMS current by order and compare THD/TDD against plant quality targets before tuning line reactors or passive filters. | PCC location, demand-current reference, meter bandwidth class |
| Voltage quality screening | Confirm bus voltage waveform quality for sensitive automation devices | Use Voltage THD mode and monitor dominant orders to determine whether distortion is source-side or load-side coupled. | Instrument transformer ratio, grounding quality, sampling interval |
| Transformer thermal review | Evaluate harmonic-related transformer stress trend | Use Current THD mode and K-factor result as a fast pre-check to decide if detailed thermal loading analysis is required. | Transformer nameplate K-rating, ambient temperature, duty cycle |
Related Tools
Power Factor Correction Calculator
LiveAnalyze reactive-power compensation after distortion screening.
Open tool3-Phase Power Calculator
LiveCross-check real, reactive, and apparent power relationships.
Open toolSingle-Phase Power Calculator
LiveEvaluate single-phase feeders where harmonic currents are measured.
Open toolTransformer kVA Calculator
LiveEstimate loading baseline before deeper harmonic thermal checks.
Open toolShort-Circuit Current Calculator
LivePair power quality checks with available-fault-current assumptions.
Open tool