Motor Overload Relay Setting Calculator
Motor Overload Relay Setting Calculator supports engineering calculations with transparent assumptions, practical result interpretation, and links to next-step technical resources.
Formula
IFLC = Pout / (sqrt(3) x V x eta x PF)
Iset range = IFLC x [100% .. 115/125%] x AmbientFactor
Startup stress = (Istart / IFLC)^2 x tstart
Trip envelope: tlimit = Class x (7.2 / Iratio)^2
This tool is a front-end relay setting estimator. Final settings should be validated against relay manufacturer curves, motor thermal limits, and project protection coordination requirements.
Protection Loop
Trip Class Curves (Dynamic)
Relay Decision
Awaiting valid inputs
Recommended class: --
Overload Relay Setting Fundamentals
Thermal Protection Window
Set too low: nuisance trips during normal load transitions.
Set too high: delayed overload response and potential motor stress.
Trip Class Fit
Class behavior must align with startup current and acceleration duration.
Startup envelope mismatch is a frequent root cause of commissioning trips.
Equation Matrix
| Topic | Equation | Meaning |
|---|---|---|
| Motor full-load current | IFLC = Pout / (sqrt(3) x V x eta x PF) | Base relay setting reference for three-phase motors from electrical and mechanical assumptions. |
| Overload setting range | Iset in [IFLC x 100%, IFLC x 115/125%] x AmbientFactor | Practical setting window based on service factor and ambient influence assumptions. |
| Startup stress index | Stress = (Istart / IFLC)^2 x tstart | Fast screening metric for selecting trip class robustness against motor acceleration events. |
| Trip-class envelope | tlimit = Class x (7.2 / Iratio)^2 | Approximate time-current envelope for comparing startup profile against selected class behavior. |
Commissioning Workflow Matrix
| Scenario | Objective | Recommendation | Critical Checks |
|---|---|---|---|
| Motor branch protection commissioning | Set overload relay for reliable startup without nuisance tripping | Calculate FLC first, then tune setpoint inside allowable range based on service factor, ambient, and measured load profile. | Actual running current, acceleration time, process duty cycle |
| Starter-type migration project | Re-check overload class after switching DOL to soft starter or VFD | Update startup multiplier and start time assumptions, then compare selected trip class margin before field rollout. | Ramp profile, torque demand, bypass mode transitions |
| Maintenance troubleshooting | Diagnose frequent overload trips under known process conditions | Compare measured startup events with class envelope and setting range to identify if trips are thermal-true or setting-driven. | Mechanical drag, voltage sag, relay health and calibration |
Frequently Asked Questions
Related Tools
Motor Full-Load Current Calculator
LiveEstimate rated running current before overload relay setpoint decisions.
Open toolMotor Starting Current Calculator
LiveRefine startup multiplier assumptions used in overload trip-class checks.
Open toolFuse Sizing Calculator
LiveCoordinate overload behavior with branch protection sizing assumptions.
Open toolBreaker Sizing Calculator
LiveCross-check feeder breaker selection once overload settings are proposed.
Open tool3-Phase Power Calculator
LiveValidate power, PF, and current relationships around motor protection workflows.
Open tool