Generator Sizing Calculator supports engineering calculations with transparent assumptions, practical result interpretation, and links to next-step technical resources.
Formula
Srun = Ptotal / PF
Stransient = Srun + (Smotor,start - Smotor,run)
Sbase = max(Srun × (1 + reserve), Stransient)
Sderated = Sbase / (Ftemp × Faltitude)
Sfinal = max(Sderated, Stransient / load-step-limit)
Preliminary screening model for generator frame selection. Final design should verify voltage dip, frequency recovery, alternator reactance, and site-specific standards.
Power Flow
Start Event Envelope
Steady vs Transient
Steady-state demand sets baseline loading.
Largest motor start often controls instantaneous source stress.
Environmental Derating
High ambient and altitude reduce practical deliverable capacity.
Ignoring derating can hide undersizing until commissioning.
| Topic | Equation | Meaning |
|---|---|---|
| Running apparent load | Srun = Ptotal / PF | Base continuous apparent load that the generator must support in steady operation. |
| Startup transient load | Stransient = Srun + (Smotor,start - Smotor,run) | Largest motor startup adds transient burden above normal running condition. |
| Derated requirement | Sderated = Sbase / (Ftemp × Faltitude) | Ambient temperature and altitude reduce practical generator output capability. |
| Load-step requirement | Sstep = Stransient / load-step-limit | If a generator accepts only limited single-step loading, larger frame size may be required. |
| Scenario | Objective | Recommendation | Critical Checks |
|---|---|---|---|
| Prime-power generator framing | Choose practical kVA frame before vendor RFQ | Use realistic running PF and largest motor startup multiplier, then apply reserve and site derating before selecting standard frame. | Voltage dip target, frequency recovery, alternator class |
| Standby source with motor starts | Avoid nuisance undervoltage trip during restart events | Model worst-case first-start transient and confirm load-step capability does not become the dominant sizing constraint. | ATS sequence, staggered starts, protective relays |
| High-altitude or high-ambient deployment | Prevent hidden undersizing from environmental derating | Treat thermal and altitude derating as explicit factors rather than post-hoc safety margin additions. | Site meteorology, enclosure ventilation, maintenance intervals |
Related Tools
Motor Starting Current Calculator
LiveEstimate startup inrush profile used as transient input for generator sizing.
Open tool3-Phase Power Calculator
LiveCross-check power and current relationships for balanced three-phase systems.
Open toolBattery Backup Runtime Calculator
LiveEvaluate backup runtime behavior after generator and load assumptions are set.
Open toolTransformer kVA Calculator
LiveCompare kVA context across transformer and generator infrastructure decisions.
Open toolVoltage Drop Calculator
LiveCheck feeder performance once source and load assumptions are frozen.
Open tool